Page 84
WAGO MCS DC power connector
-48VDC Power Supply (removed from back panel)
Input voltage: -48VDC
Minimum voltage: -40 VDC
Maximum voltage: -60 VDC
Maximum operating current: 0.5A
The DC power source must be:
Electrically isolated from any AC source
Reliably connected to earth ground
Capable of providing up to 100 Watts of continuous power
D.2: Over-Current Protection
Over-current protection requirements:
10 Amp fast trip
Double pole
DC rated
Over-current protection devices (e.g., circuit breakers) must be provided as part of each
equipment rack and are not included with the Console Server. The device must be
located between the DC power source and the Console Server.
D.3: DC Supply Connector
The supply input connectors are provided with each Console Server; the conductors
are not.
Conductor specifications:
Material: copper only
Wire gauge: 16 AWG
Insulation rating: 75 °C
minimum, low smoke-fume, flame retardant Branch
circuit cable.
Insulation color: per applicable national electrical codes.
Grounding cable insulation color: green/yellow